Utility Chiller, Gas Boiler & Air Compressor Replacements

Innovative Solutions

ITAC performed the removal and replacement of mechanical equipment for power generation systems at multiple facilities, including:

  • Chiller Replacement: Removed existing 1K ton steam turbine driven chiller (evaporator, condenser, compressor, steam turbine, oil lubrication, and refrigerant recovery systems). Installed 1K ton electric motor driven chiller and new foundation, equipment, piping, and controls. Refurbished existing 2.3 kV substation and provided new electrical service to the chiller. Installed a starter cabinet at the chiller and Modbus communications between the chiller controller and owner’s DCS.
  • Natural Gas Boilers Replacement: Installed: two natural gas fired steam boilers (85M BTU/hr) to generate 300 psig steam; pressure reducing stations to produce 20 psig, 75 psig, and 180 psig steam; new foundation, equipment, piping, 480 V electrical service and cable trays, and process controls. Connected the burner management system, boiler controller, and owner’s DCS.
  • 400 hp Air Compressor Replacement: Removed two 125 hp reciprocating air compressors. Installed two 400 hp, 1700 scfm, two stage, rotary screw air compressors, two after-aftercoolers, new foundations, equipment, piping, and controls. Provided new 480 V electrical service to the compressors and disconnected VFD for each compressor. Installed Modbus communications between the compressor controllers and owner’s DCS.
  • 2000 hp Chiller Replacement: Removed Elliott steam turbine driven air compressor, existing piping, controls wiring, and concrete. Installed a 2000 hp, 9100 scfm, three-stage, rotary screw air compressor, new foundations, equipment, piping, controls, a 4200 kVA, 12kV/4180V transformer, a 12-kV electrical service substation to the transformer, and transformer protection relays. Installed a refurbished medium voltage motor control center (MCC) and 4180V electrical service, motor protection relays, power meter, Bently Nevada vibration monitoring system, and Modbus communications between the compressor controllers and owner’s DCS.